Cullerin Range Wind Farm

Essential Energy

Generator name: Cullerin Range Wind Farm
Location Lerida Road North, Cullerin NSW
Date Connection Point commissioned 1 July 2009
Technology of generating unit 15 x 2MW Wind Turbines
double fed induction generators
Generating unit - make and model REpower - type MM82 and MM92
Generation capacity (maximum) 30MW @ 132kV
Contribution to fault level S5.2.8 @ 1pu volts
3ph - 0.4kA
1ph - 0.0kA
ph - ph 0.35kA
Size and rating of relevant transformer 1 x 132/22kV 32MVA - YNynD
Connection Arrangement SLD View the SLD
Protection systems differential and over current
Telecommunication systems SCADA
Voltage control system Voltage regulation scheme
Reactive power capability 11.8 MVAr
Site specific conditions Target voltage range – max. 1.07pu


Safety for your work site

Safety for your work site